FD30 fire doors for Maidenhead buildings
Our FD30 fire doors service covers Maidenhead and the wider Berkshire area. Every job starts with a survey of the openings, so the quote reflects your actual doors rather than a guess.
Buildings in and around Maidenhead range from houses with integral garages to industrial estates and schools. Whatever the building, the standard is the same: certified products, correct gaps, seals and closers, and a frame sealed to the wall.
In Maidenhead, FD30 doors are the usual choice for escape-route corridors, stairs and kitchen doors where the fire strategy asks for 30 minutes. Each FD30 leaf we supply for Maidenhead is sized for the opening, rather than trimmed beyond what its certification allows.
What does a correct FD30 installation include?
A typical timber FD30 leaf is around 44mm thick and hangs on at least three fire-tested hinges. The gaps between leaf and frame are set to the manufacturer's data, usually around 3mm. Intumescent strips, and smoke seals where needed, go in the frame or leaf edge as specified. The closer must pull the door shut and latch it from any angle. Every hole cut for a lock, latch or hinge is lined with intumescent material where the certification calls for it.
Then comes the part that is often skipped: sealing the gap between the frame and the wall with a tested material, as BS 8214:2026 now sets out in more detail.
Each installation includes:
- Certified FD30 or FD30S leaf, or full doorset
- Fire-tested hinges, latch or lock and intumescent pads
- Photo record, product data and certificate references at handover
- Frame-to-wall gap sealed with an evidenced material
What the rules say for Maidenhead
The rules that apply to fire doors in Maidenhead are England's. The responsible person under the Regulatory Reform (Fire Safety) Order 2005 must keep fire doors in non-domestic premises and the common parts of flats in working order; the Fire Safety Act 2021 confirmed that this includes flat entrance doors onto common parts.
Where a Maidenhead block is above 11 metres, regulation 10 of the 2022 regulations means communal doors are checked every three months and flat entrance doors annually on a best-endeavours basis. Replacement doors must also satisfy the Building Regulations, with Approved Document B as the guidance most building control bodies work from.
Which buildings in Maidenhead need FD30 fire doors?
The need for FD30 fire doors usually arises in HMOs or offices, and sometimes schools. Each has its own pressures, such as residents at home or a building that must stay open, so we plan the sequence of work in Maidenhead to keep escape routes protected throughout.
From enquiry to handover in Maidenhead
- Measure the opening, check the frame and confirm the rating needed
- Order a certified leaf or doorset to size, with matching components
- Remove the old door and assess the frame or structural opening
- Fix the frame and hang the leaf to the certified gap tolerances
- Fit seals, hinges, latch, closer and signage, then test close-and-latch
- Seal the frame-to-wall gap, make good and record the evidence
Guide prices in Maidenhead
As a guide, budget £300–£600 for a leaf into a sound existing frame; £650–£1,300 for a doorset, ex VAT for FD30 fire doors. The figure for your Maidenhead building depends on the number of doors, the rating, the condition of the frames, finishes, hardware and access. We confirm a fixed price after the free survey.
Maidenhead and neighbouring towns
Neighbouring towns such as Slough, Windsor, High Wycombe and Bracknell are covered too, so clients with several buildings can use one installer and one evidence format.
Common questions
Do you cover SL6 and nearby postcodes?
Yes. We cover Maidenhead including SL6, and nearby towns such as Slough and Windsor. The survey and written quote are free.
Can you work from an existing inspection report for my Maidenhead building?
Yes. Send it over and we can often price straight from it, then confirm on site. We report back against the same door references so you can close actions off.
What is the difference between FD30 and FD30S?
FD30S has been tested for smoke control as well as fire. It adds a smoke seal, usually a brush or blade, and needs a tight threshold gap. Flat entrance doors and doors onto protected escape routes are commonly specified as FD30S.
How long does it take to fit an FD30 door?
A leaf into a sound frame is often a few hours. A full doorset including frame removal, fixing, sealing and making good is usually half a day to a day per opening, depending on access and the wall construction.